| Input (DC) |
|
| Recommended max. PV input power |
30 kWp |
| Max. PV input voltage |
1100 V * |
| Min. PV input voltage / Start-up input voltage |
180V / 180V |
| Rated input voltage |
600 V |
| MPP voltage range |
160V-1000V |
| No. of independent MPP inputs |
2 |
| No. of PV strings per MPPT |
2 / 2 |
| Max. PV input current |
50 A (25 A / 25 A) |
| Max. DC short-circuit current |
64 A (32 A / 32 A) |
| Max. current for input connector |
30 A |
| Output (AC) |
|
| Rated AC output power |
20000 W |
| Max. AC output apparent power |
22000 VA** |
| Rated AC output apparent power |
22000 VA** |
| Max. AC output current |
31.9 A |
| Rated AC output current(at 230V) |
29 A |
| Rated AC voltage |
3 / N / PE, 220 / 380 V |
| AC voltage range |
3 / N / PE, 230 / 400 V |
| Rated grid frequency |
3 / N / PE, 240 / 415 V |
| Grid frequency range |
180V – 276V / 311V - 478V |
| Harmonic (THD) |
<3% (at rated power) |
| Power factor at Rated power / Adjustable power factor |
>0.99 / 0.8 leading – 0.8 lagging |
| Feed-in phases / Connection phases |
3 / 3 |
| Efficiency |
|
| Max. efficiency |
98.5% |
| European efficiency |
98.1% |
| Protection&Function |
|
| Grid monitoring |
Yes |
| DC reverse connection protection |
Yes |
| AC short-circuit protection |
Yes |
| Leakage current protection |
Yes |
| Surge Protection |
DC Type II / AC Type II |
| Ground fault monitoring |
Yes |
| DC switch |
Yes |
| PV String current monitoring |
Yes |
| Arc fault circuit interrupter (AFCI) |
Yes |
| PID recovery function |
Yes |
| General Data |
|
| Dimensions(WHD) |
370 * 480 * 195 mm |
| Weight |
21 kg |
| Mounting method |
Wall-mounting bracket |
| Topology |
Transformerless |
| Degree of protection |
IP65 |
| Night power consumption |
< 6 W |
| Corrosion |
C5 |
| Operating ambient temperature range |
-25 ℃ to 60 ℃ |
| Allowable relative humidity range (non-condensing) |
0% – 100% |
| Cooling method |
Smart forced air cooling |
| Max. operating altitude |
4000 m |
| Display |
LED |
| Communication |
WLAN / Ethernet / RS485 / DI / DO |
| DC connection type |
MC4 (Max. 6 mm² ) |
| AC connection type |
Plug and play |
| Grid Compliance |
IEC / EN 61000-6-1/2/3/4, IEC 61000-3-2/3/11/12, IEC / EN62109-1/2, IEC 61727, IEC 62116, IEC 61683, IEC 60068-2-1/2/14/30/64/27,IEC TS 62910 , EN50530, AS/NZS 4777.2:2020, VDE-AR-N-4105, DIN VDE0126-1-1/A1, EN50549-1, DEWA, VFR 2019, UTE C15-712-1, PSE NC RfG, UNE 206006/7 IN, MEA/PEA, G98, UNE 217002:2020, NTS V2 TypeA |
| Grid Support |
LVRT, HVRT,active & reactive power control and power ramp rate control |